Chassis Ground Connection Installation
Before you connect power or turn on power to your router, you must provide an adequate chassis ground (earth) connection
for the router chassis. A ground connector is provided on each Cisco ASR 1006 Router. See Figure 7.
Caution The dual-lug chassis stud must be installed, the SIP and SPA must be fully inserted and screwed in and earthed to
prevent a potential hazard in a telecom line.
Have the recommended tools and supplies available before you begin this procedure: Phillips screwdriver, dual-lug chassis
ground component, and grounding wire.
Step 1 Use the wire stripper to strip one end of the AWG #6 gauge wire approximately 0.75 inches (19.05 mm).
Step 2 Insert the AWG #6 gauge wire into the wire receptacle on the grounding lug.
Step 3 Use the crimping tool to carefully crimp the wire receptacle around the wire; this step is required to ensure a proper
mechanical connection.
Step 4 Attach the grounding lug with the wire so the grounding wire does not overlap the power supply.
Figure 7 Attaching a Grounding Lug to the Chassis Ground Connector
Step 5 Locate the chassis ground connector on the side of your chassis.
Step 6 Insert the two screws through the holes in the grounding lug.
Step 7 Use the Number 2 Phillips screwdriver to carefully tighten the screws until the grounding lug is held firmly to the
chassis. Do not overtighten the screws.
1
Chassis earth ground studs and lead wire
3
Earth ground connector on the chassis
2
Grounding screws
4
Earth ground symbol