Cisco Systems ASR 1006 Rychlý návod Strana 22

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 44
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 21
22
Figure 16 DC Power Supply Terminal Block Positive and Negative Connections
Step 5 Tighten the Kepnut screw to recommended torque of 18 in-lbs minimum to 22 in-lbs maximum for the positive stud
and wire.
Note Secure the wires coming in from the terminal block so that they cannot be disturbed by casual contact.
Step 6 Use tie wraps to secure the wires, so that the wires are not pulled from the terminal block by casual contact. Ti-wrap
studs are located below the power supply terminal block
Step 7
Replace the terminal block plastic cover and tighten the screw. The plastic cover is slotted and keyed to fit correctly over
the terminal block.
See Figure 17.
280311
Zobrazit stránku 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 43 44

Komentáře k této Příručce

Žádné komentáře